Figure 22 Internal Circuits Window - Secutron MR-2200 Programming Manual

Fire alarm control panel
Hide thumbs Also See for MR-2200:
Table of Contents

Advertisement

Internal Circuit 99, Common Trouble: This circuit is tripped by any internal circuit or
trouble condition not associated with an internal circuit that turns on the Common
Trouble LED on the panel. This circuit is used to annunciate common trouble conditions
at a remote location. This circuit is not tripped by troubles generated by input circuits or
addressable devices. This circuit is not recorded in the archive of the panel.

Figure 22 Internal Circuits Window

2.10.2 Internal Circuits List
The Internal Circuits List displays all of the internal circuits for the current Control Panel. Each
line includes the internal circuit number, its description and if relates have been assigned.
Warning: Some of the internal circuits (e.g. checksum) do not have restore signals associated
with them. They generally relate to a condition that requires either service work or a reboot of
the panel. Any relates assigned to such an internal circuit have no way to be reset short of re-
booting the entire network.
2.10.3 Pushbuttons
The following push buttons are available:
List Entries: This new feature allows the user to control the information displayed.
Relevant only lists items applicable to the current version only. All lists all possible items
so that relates made on previous versions may be removed.
Exit: Closes the Internal Circuits Window and returns to the Panel Window.
Reset: Clears all relates associated with the current internal circuit.
Relate: Opens the Relate Window for the internal circuit. This allows for the
programming of outputs, LEDs, relays and control modules to be operated by the
internal circuit.
Copy Relates: Copies the relates from another input to the current internal circuit (see
Figure 21). The values of the panel and circuit are required. Press Copy to copy the
information. If the function type of the two circuits is different, a requester is presented to
confirm the copy.
Map: Displays and/or updates the Map Window. See section 2.8 Map Window of the
Modul-R Human Interface User Guide.