2.3.19 Pushbuttons
The System Window has the following push buttons on the right hand side:
Exit: Closes the System Window and, if editing, causes the database to be saved. After
an edit session, a requester asks if the database should be Verified. A database has to
verify without errors before it can be downloaded.
Panels: Displays the Panel Window. If no panel is currently defined, the Add Panel Box
is displayed.
Switches: Displays the Switches Window. This window determines which devices are
attached to the switches and the timers associated to each switch. See section 2.4

Switches Window.

Groups: Displays the Groups Window. This window is used to define groups of relates.
See section 2.5 Groups Window.
Map: Displays and/or updates the Map Window. See section 2.8 Map Window of the
Modul-R Human Interface User Guide.
Verify List: Displays the Verify List. If there is no Verify List, a requester will appear
asking whether you wish to perform a verification. See section 2.6.5 of the Modul-R
Human Interface User Guide for a full description of the Verify List and its uses.
Settings: Defines the Verify warnings to disable and/or errors to reduce to warnings for
the current database. Not all warnings/errors can be disabled/reduced. The use of this is
not recommended, but provided for special circumstances.
2.4
Switches Window
2.4.1 Overview
The Switches Window (see Figure 6) allows for the setting of the On/Off (Day/Night) switches.
There are 16 system wide switches available. All panels in the network keep track of their
portion of the devices related to each switch. Relays, LEDs and control modules follow the On/
Off state of the switch they are related to. Addressable sensors use Day sensitivity while the
switch is on and Night sensitivity while the switch is off. The timers can be used to have the
switch change state at set times each day. Switches can be operated manually at the panel
whether they have timers or not. If the Switch is associated to a Hot Key, the Hot Key then
operates the switches, causing the related LEDs, relays and control modules to react.
Editing MHI Databases