Addressable Devices; Figure 3 Panel Removed From Network - Secutron MR-2200 Programming Manual

Fire alarm control panel
Hide thumbs Also See for MR-2200:
Table of Contents

Advertisement

If there is break in a communications link (see Figure 2) the broadcast is disposed of by the
unit unable to pass it on. In the situation where a unit has been removed from the loop (see
Figure 3), the broadcast is passed only from com2 to com1 at the jump. In Figure 3, panel 5
passes the broadcast to panel 3, but panel 3 will not pass the broadcast on to panel 5 since it
is supposed to be communicating to panel 4.
M R 2 2 0 0
I D # 1
C O M 2
Figure 3
Panel Removed from Network
1.4

Addressable Devices

1.4.1 Supported Devices
The MR-2200 can use analog/addressable devices. There are two general types of devices:
sensors and modules. The following devices are supported:
MRI-M500DM
MRI-M500M
MRI-M501M
MRI-M502M
MRI-M500S
Modules
MRI-M500R
MRI-M500X
IM-10
CZ-6
CR-6
SC-6
M R 2 9 0 0
I D # 2
C O M 1
C O M 2
M R 2 2 0 0
I D # 5
C O M 1
C O M 2
Dual Input Monitor Module
Monitor module, Classes A/B initiating
Mini Monitor module, Class B initiating
Monitor Module for 2- wire smoke detectors Classes A/B
initiating
Control module
Relay Module
Fault isolator module
Intelligent Input Monitor Module
Zone Interface Module
Control Module Relay
Supervised Control Module
Operation and Programming Concepts
M R 2 9 4 4
I D # 3
C O M 1
C O M 2
M R 2 9 4 4
I D # 4
C O M 1
C O M 2
C O M 1
5