Operation And Programming Concepts; Introduction - Secutron MR-2200 Programming Manual

Fire alarm control panel
Hide thumbs Also See for MR-2200:
Table of Contents

Advertisement

1.0
Operation and Programming
Concepts
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in CAN/ULCS527, Standard for Control Units for Fire Alarm Systems, certain programming
features or options must be limited to specific values or not used at all as indicated below.
Program feature or
option
Bell System
Bell Cutoff
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in UL864, Standard for Control Units for Fire Alarm Systems, certain programming features or
options must be limited to specific values or not used at all as indicated below.
Program feature or
option
AC Fail
Bell Cutoff
1.1

Introduction

This chapter provides an overview of the MR-2100/2200's (hereafter called the MR-2200)
features and supported devices.
Permitted in CAN/
ULCS527? (Y/N)
Y
Y
Permitted in UL864?
(Y/N)
Y
N

Operation and Programming Concepts

Possible settings\methods
Alert, Evac, Alert/Evac,
Staged
0 or 5 to 30 minutes
Possible settings\methods
0 to 30 hours
0 or 5 to 30 minutes
Settings permitted in
CAN/ULCS527
Alert, Evac
All
Settings permitted in
UL864
1, 2 or 3 hours
0
1