6.5.8
Connecting the encoder to the SMC30 Sensor Module
Safety instructions
NOTICE
Damage caused by incorrectly connected external encoder
If the external encoder is not connected or operated correctly, this can damage the
components.
● Only one measuring system can be connected to each sensor module. The sensor module
Procedure
1. Carefully comply with the 5 safety rules.
2. Allow unimpeded access to the SMC30 Sensor Module.
3. Route the cables from the encoder into the cabinet from below and to the encoder module.
4. Connect the encoder cables
SINAMICS SM150 6SL3815-7NP41-0AA1
Operating Instructions Rev.201910281301 EXAMPLE
is wired internally to the customer terminal strip. For further information, see the circuit
manual.
①
to the SMC30 Sensor Module.
Electrical connection
6.5 Connection
111