Replacing The Precharging Transformer - Siemens SINAMICS SM150 6SL3815-7NP41-0AA1 Operating Instructions & Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

9.5.11

Replacing the precharging transformer

Danger to life as a result of incorrect replacing the precharging transformer
Replacing the precharging transformer incorrectly can result in death, serious injury, or
material damage.
● Follow "the five safety rules (Page 15)".
● Before replacing the precharging transformer, open the safety disconnector for the 400 V
● Lift the transformer carefully because it is heavy (> 45 kg).
Removing the precharging transformer
1. Detach the high-voltage cables
2. Detach the 400 V connecting cables
3. Detach the grounding cable
4. Remove the fixing screws
5. Remove the transformer.
Figure 9-13
SINAMICS SM150 6SL3815-7NP41-0AA1
Operating Instructions Rev.201910281301 EXAMPLE
WARNING
supply.
Replacing the precharging transformer
.
.
.
at the front and rear on the base brackets.
Maintenance
9.5 Repair
173