Siemens SINAMICS SM150 6SL3815-7NP41-0AA1 Operating Instructions & Installation Instructions page 129

Medium-voltage drive
Table of Contents

Advertisement

List of signals for the analog outputs
Signal
Speed setpoint for setpoint filter
Motor speed unsmoothed
Actual speed smoothed
Output frequency
Output current
DC-link voltage
Torque setpoint
Output power
For diagnostic purposes
Control deviation
Slip frequency
Phase current actual value
Control factor
Field-generating current setpoint
Field-generating actual current
Torque-generating current setpoint
Torque-generating actual current
Flux setpoint
Actual flux
DC-link voltage
Phase voltage
For further diagnostic purposes
Speed controller output
I component of speed controller
Scaling
Variable
Reference speed
Reference voltage
Reference current
Reference torque
Reference power
Reference frequency
Reference control factor
Reference flux
Reference temperature
SINAMICS SM150 6SL3815-7NP41-0AA1
Operating Instructions Rev.201910281301 EXAMPLE
Parameter
r0060
r0061
r0063
r0066
r0068
r0070
r0079
r0082
r0064
r0065
r0069
r0074
r0075
r0076
r0077
r0078
r0083
r0084
r0088
r0089
r1480
r1482
Scaling parameter
100% = p2000
100% = p2001
100% = p2002
100% = p2003
100% = r2004
100 % = r2000 / 60
100% = Maximum output voltage
without overload
100% = Rated motor flux
100% = 100° C
8.5 Functions
Unit
Scaling
(100% = ...)
1/min
p2000
1/min
p2000
1/min
p2000
Hz
Reference fre‐
quency
Aeff
p2002
V
p2001
Nm
p2003
kW
r2004
1/min
p2000
Hz
Reference fre‐
quency
A
p2002
%
Reference control
factor
A
p2002
A
p2002
A
p2002
A
p2002
%
Reference flux
%
Reference flux
V
p2001
V
p2001
Nm
p2003
Nm
p2003
Default for quick commissioning
p2000 = Maximum speed (p1082)
p2001 = 1000 V
p2002 = Current limit (p0640)
p2003 = 2 x rated motor torque
r2004 = (p2003 x p2000 x pi) / 30
Operation
129