3.6.21

Safety locking system (option M10)

The safety locking system is based on the key transfer system developed by Castell. It is a
supplementary mechanism to the electromechanical door locking system integrated as
standard. The medium-voltage breaker must be opened before access can be gained to the
coded key of the key exchange unit. The opened medium-voltage breaker releases the key to
the key exchange unit. This key enables the access to the keys for the cabinet doors of the
power unit. This key interlocking system ensures that the converter is disconnected from the
medium-voltage supply and that no cabinet components are connected to medium voltage. As
long as the cabinet doors are not closed again and the keys to the power-unit cabinet are not
inserted back in the key exchange unit, the key for the medium-voltage breaker will not be
released. The medium-voltage breaker cannot be switched on again.
See also
Secure locking system (option M10) (Page 155)
3.6.22

Power cable connection at the drive input from above (option M13)

You can introduce the line-side power cable into the cabinet from the top.
3.6.23

Extended dust protection (option M16)

The dust protection cover made from polycarbonate (Makrolon) protects the drive during
installation and before commissioning from the ingress of dust and chips.
See also
Removing the dust protection cover (Page 94)
3.6.24
Signal and control cable (max. 2.5 mm²) (option M32)
Signal and control cables are connected directly to the terminals on Terminal Module TM31 or
TM15 as standard. The maximum connectable cross-section for these cables to the TM31 and
TM15 Terminal Modules is limited to 1.5 mm
With option M32, you can connect signal and control cables with connection cross-sections of
up to 2.5 mm
3.6.25

Suitability for marine use (option M66)

The converter design corresponds to the requirements of the following classification societies.
● Lloyds Register
● American Bureau of Shipping
SINAMICS SM150 6SL3815-7NP41-0AA1
Operating Instructions Rev.201910281301 EXAMPLE
to a terminal strip via cage clamp terminals.
2
.
2
Description
3.6 Description of options
71