5.7 Connecting The Dc Bus - Siemens SINAMICS SM150 6SL3815-7NP41-0AA1 Operating Instructions & Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

Installation

5.7 Connecting the DC bus

Preparing the contact surfaces of the link rails
1. Clean the contact surfaces until the bare metal surface is exposed and has a shiny
2. After abrading the contact surfaces, clean them immediately with a clean cloth soaked in
3. Apply a thin film of grease provided to the contact surfaces of the link rails immediately after
4. Bolt the link rails together within one hour.
5.7.2
Connecting the DC bus
Fixing points at the top and bottom at the DC bus
Figure 5-4
Connecting the DC bus
1. Place the flexible copper bars on the top of the DC bus.
2. Screw the upper busbars to the left and right at the appropriate mounting points
3. Screw the lower busbars to the left and right at the appropriate mounting points
92
appearance. Use an abrasive paste, for example Schleiffix, universal cleaner from
Klingspor, type No.: 120.
ethanol.
cleaning.
CAUTION
Damage to paint surfaces, cables and plastic parts and components caused by grease
The grease attacks paint surfaces, cables, contact parts & components etc.
● Do not allow the grease to come into contact with any of these parts and components.
Remove the grease immediately if it does come into contact with any of these parts.
M5 nuts, washers and locking washers provided. Use a tightening torque of 3 Nm.
M5 nuts, washers and locking washers provided. Use a tightening torque of 3 Nm.
SINAMICS SM150 6SL3815-7NP41-0AA1
Operating Instructions Rev.201910281301 EXAMPLE
using the
using the

Advertisement

Table of Contents
loading

Table of Contents