Diagnostics Via Parameters - Siemens SINAMICS SM150 6SL3815-7NP41-0AA1 Operating Instructions & Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

8.6.3.3

Diagnostics via parameters

Diagnostic parameters for the device status
r0002
Drive status
Display of drive status
r0046
Missing drive enable signals
Display of the missing enable signals that prevent the drive control from being commissioned
Bit
Signal name
00
OFF1 enable missing
01
OFF2 enable missing
02
OFF3 enable missing
03
Enable run missing
05
External power-on inhibit active
06
Commissioning not yet complete
09
Infeed enable missing
10
Ramp-function generator enable missing
11
Ramp-function generator start missing
12
Setpoint enable missing
13
PSA pulse inhibit due to undervoltage
14
Operation enable from automatic restart function
16
OFF1 internal enable missing
17
OFF2 internal enable missing
18
OFF3 internal enable missing
19
Pulse enable internal missing
24
Motor data set changeover active
25
Function bypass active
26
Drive inactive or not operational
r0050
Active command data set (CDS)
Display of the active command data set (Command Data Set, CDS)
Bit
Signal name
00
CDS effective, bit 0
01
CDS effective, bit 1
02
CDS effective, bit 2
03
CDS effective, bit 3
You can find additional notes in the parameter description of parameters p0810, p0811, r0836 in the List Manual.
The command data set selected via the binector inputs (e.g. p0810) is displayed via r0836.
SINAMICS SM150 6SL3815-7NP41-0AA1
Operating Instructions Rev.201910281301 EXAMPLE
Operation
8.6 Fault and system messages
0-signal
1-signal
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
0-signal
1-signal
No
Yes
No
Yes
No
Yes
No
Yes
145