Acceptance Certificate - Siemens SINAMICS SM150 6SL3815-7NP41-0AA1 Operating Instructions & Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

3.6.12.7

Acceptance certificate

Factory No. (see rating plate)
End customer
Connecting cable between the delivery units is plugged in from transfer
module =.T-X111 to transfer module =.T-X211
External wiring (mushroom pushbutton / activation, circuit breaker) is in ac‐
cordance with the circuit overview (section "Circuit overview")
The requirements for mushroom pushbutton / activation are fulfilled (see
section "Description" for the requirements)
The equipment is visible from the site of acknowledgement
The requirements for circuit breakers are fulfilled (see section "Description"
for the requirements)
Set delay time for safety relay -K110
Set delay times for time relay -K120
Tripping level of voltage monitoring relay -A11 checked (25.2 V - 26.4 V).
(For test steps, see "Commissioning", section "Checking voltage monitoring
relay -A11")
"Safe Torque Off" function test executed. (For test steps, see "Commission‐
ing", section ""Safe Torque Off" function test")
Log completion and countersignatures
Date
Date
SINAMICS SM150 6SL3815-7NP41-0AA1
Operating Instructions Rev.201910281301 EXAMPLE
The points listed in the acceptance certificate are hereby confirmed
Commissioning engineer
Name
Machine manufacturer or authorized department
Name
3.6 Description of options
Company/dept.
Company/dept.
Description
N-
_______ seconds
_______ seconds
Signature
Signature
63