Table 8-5 Leds Of The Dm10 Diagnostics Module - Siemens SINAMICS SM150 6SL3815-7NP41-0AA1 Operating Instructions & Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

Operation
8.6 Fault and system messages
LED
Color
RUN /
-
ERR
Green
Orange
Red
Green/red
Green/
orange
or
Red/orange
LEDs of the DM10 diagnostics module
The LEDS installed on the diagnosis module indicate the logic state of the signals present
between the communication partners of the DM10 diagnosis module.
Table 8-5
LEDs of the DM10 diagnostics module
LED
Communication partner
H30
-X232/-X32
H31
-X232/-X32
H32
-X232/-X32
H33
-X232/-X32
H34
-X33/-X5
H35
-X33/-X5
H36
-X33/-X5
H37
-X33/-X5
H20
-X34/-X36
H21
-X34/-X36
H22
-X35/-X36
H23
-
144
Status
Description; cause
Off
The electronic power supply is missing or
lies outside the permissible tolerance
range.
Continuous
The component is ready for operation
light
and cyclic DRIVE-CLiQ communication
is in progress.
Continuous
DRIVE-CLiQ communication is being es‐
light
tablished.
Continuous
At least one fault is present in the com‐
light
ponent.
LED is controlled irrespective of the cor‐
responding messages being reconfig‐
ured.
0.5 Hz flashing
Firmware download in progress.
light
2 Hz flashing
Firmware download is complete. Waiting
light
for POWER ON.
Flashing light
Component recognition via LED is acti‐
vated.
The color depends on the LED state
when component recognition is activated.
Meaning: signal 1 / signal 0
Control signals from PSA present / not present
Control signals from PSA present / not present
Control signals from PSA present / not present
Control signals from PSA present / not present
Binary plant signals for diagnosis on PADU8 present / not present
Binary plant signals for diagnosis on PADU8 present / not present
Binary plant signals for diagnosis on PADU8 present / not present
Binary plant signals for diagnosis on PADU8 present / not present
Internal power supply 1P24 OK / not OK
Internal power supply 1N24 OK / not OK
External power supply 2P24_1 and 2P24_2 OK / 2P24_1 or 2P24_2 not OK
Internal and external power supplies OK / not OK
Remedy
-
-
-
Remedy and acknowledge fault.
-
Carry out a POWER ON.
-
SINAMICS SM150 6SL3815-7NP41-0AA1
Operating Instructions Rev.201910281301 EXAMPLE

Advertisement

Table of Contents
loading