Description
3.6 Description of options
Adjusting the -K110 and -K120 delay times
A
B
Figure 3-13
The delay times set at the factory can be changed by the customer using the closed-loop
controllers. Change the settings of the time relay -K120 only when it is disconnected from the
power supply.
When you plan your settings, you must comply with the following rules:
T
delay K110
*T
tolerance
If this rule is not observed, safety is not restricted in any way. However, the second switch-off
signal path via the circuit-breaker is used for each activation.
58
Safety relay -K110 ...
Off-delay time
Time relay -K120
Runtime setting in %
Time range setting
Time range display
Display function
Function selection
Safety relay -K110 and time relay -K120
> (T
+ T
delay- K120
tolerance
= 1 second
*)
Operating Instructions Rev.201910281301 EXAMPLE
SINAMICS SM150 6SL3815-7NP41-0AA1