194 • Crestron SIMPL Windows

NOTICE (CMCVT147)

Symbol S-1 in macro S-5 (Macro file c:\crestron\usrmacro\mymacro.umc) is not
supported in this control system, ignoring.
All of the control systems do not support all of the available symbols, some symbols
are excluded. When a macro is created, there is no particular control system that it is
being designed for, so all symbols are allowed. When the macro is put in a program
for a particular control system, the compiler checks to make sure all of the symbols
in the macro are supported, and if a symbol is not supported, this error message
appears.

NOTICE (CMCVT150)

Symbol S-1 is not supported in this control system, ignoring.
The symbol in the program (in this case S-1) is not implemented on the control
system for which the program is designed.

FATAL (CMCVT152)

Error determining padding value from IODEV.TIO.
The device library file could not be read. Contact Crestron for further assistance.

FATAL (CMCVT153)

Error retrieving rack compiler data from IODEV.TIO.
The device library file could not be read. Contact Crestron for further assistance.

WARNING (CMCVT154)

CNX Front panel has signals defined, but no menus have been added.
A common error when programming the LCD front panel of a CNX generation
control system is to add the menus to the front panel, but forgetting to tie the join
numbers to signal names. When this error occurs, no join numbers have been
programmed even though there are objects on the front panel that require join
numbers.

FATAL (CMCVT155)

Cannot open temporary SIMPL+ Listing file C:\TEMP\SPLUS.INF.
The compiler requires temporary space when compiling SIMPL+ modules. In this
case, the temporary file SPLUS.INF in C:\TEMP could not be created. Check to
make sure that the file is not already there, that it is not marked as READ ONLY,
that the path being used actually exists, and that there is free disk space.

WARNING (CMCVT157)

CN-TVAV has simulated NVRAM – symbols using NVRAM are reset at
startup.
Some control systems do not have NVRAM, such as the CEN-TVAV and the CN-
TVAV. The symbols that use NVRAM are mapped into regular RAM. They are still
Crestron SIMPL™ Windows