6.1 INPUT CONFIGURATION
The following table shows the list of elements that can be assigned to each input. The table is divided into groups
GROUP
ENERVISTA MII SETUP
No Definition
MASK ED 1
87 1 Disable by Input
87 2 Disable by Input
MASK ED 2
DI all functions disable
Trip Disable (by DI)
INPUTS
86B Input
86A Input
Trip Contact Close (PULSE)
Group Change
Sett. Change disable
Reset (PULSE)
Oscillo Trigger (PULSE)
General Input
6
6-4
FUNCIONALITY
Input not assigned
Disable the operation (trip) of the 87 1 function
Disable the operation (trip) of the 87 1 function
Disable the operation (trip) of every function
Disable the operation of the trip contact
'B' type contact of the latching relay
'A' type contact of the latching relay
Activates trip contact
If the input is activated the active settings group will be group 2. If it is not activated, the
active settings group will be the adjusted in General Advanced Settings
Activated, it disables the possibility that settings and active group be changed: switching
to group 2 will only be possible through digital input Group change
LEDs and latched auxiliary outputs reset
Start oscillography storage
Generic element that may be used in logic configuration.
MIB High Impedance Bus Differntial Relay
6 I/0 CONFIGURATION
6.1.2 INPUT ELEMENTS
GEK-106426B
Need help?
Do you have a question about the Multilin MIB and is the answer not in the manual?