8.10 CONTACT OUTPUTS

8.10CONTACT OUTPUTS
Check that all the outputs are open.
Set the relay as follows:
87 2 Enable
87 2 Trip Enable
87 2 Pickup level
87 2 Time Delay
Inject a current through phase A terminals equal to 0.1 amp to trip the relay. Check that the trip output (terminals A5-A6)
and auxiliary output OUT2 (terminals A7-B8) and OUT4 (terminals A7-B10) close, and the PICKUP (LED4), and OP 87A
(LED1) LEDs lights up.
Inject a current through phase B terminals equal to 0.1 amp to trip the relay. Check that the trip output (terminals A5-A6)
and auxiliary output OUT2 (terminals A7-B8) and OUT4 (terminals A7-B10) close, and the PICK UP (LED4), OP 87B
(LED2) and TRIP LEDs light up.
Inject a current through phase C terminals equal to 0.1 amp1 x In (phase) to trip the relay. Check that the trip output
(terminals A5-A6) and auxiliary output OUT2 (terminals A7-B8) and OUT4 (terminals A7-B10) close, and the PICK UP
(LED4), OP 87C (LED3) and TRIP LEDs light up.
Remove the Power Supply from the relay and check that the READY contact (terminals B5-B6) closes. Power
on the relay again and check that the READY (terminals B5-B6) contact opens.
8
8-10
NAME
VALUE
Yes
Yes
0.01
MIB High Impedance Bus Differntial Relay
87 2
UNITS
Amps
0
Seconds
8 RELAY COMMISSIONING
RANGE
Yes/No
Yes/No
0.01 – 0.04
0 - 600
GEK-106426B