Searching For All Reset Parameters And Changing Their Settings - Toshiba TOSVERT VF-AS1 Instruction Manual

The new generation high-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

Default setting (=)
Setting  to  will return all parameters to the standard values that were programmed at the factory.
sWhen this parameter is set to 3,  is displayed for a while, then switches back to the original display
( 
or
 ). Note that this setting also clears all trip history records. Trip history data will be cleared at
this time.
Trip clear (=)
Setting  to  initializes the past four sets of recorded trip history data.
* (The parameter does not change.)
Cumulative operation time clear (=)
Setting  to  resets the cumulative operation time monitor to the initial value (0 [zero] time).
Initialization of type information (=)
When a trip occurs because of a type error ( is displayed), you can clear the trip by setting  to . This
function is used to reformat a control circuit board to adapt it to an inverter, for example, when a circuit board is
removed from an inverter to use another inverter for maintenance or for other reasons. This setting clears all type
data stored in the inverter.
Save user-defined parameters (=)
Setting  to  causes all the current parameter settings to be stored individually.
Reset of user-defined parameters (=)
Setting  to  returns all parameters to the settings saved by setting the parameter =.
* The above settings  and  allows you to have your own default parameter settings.
Cumulative fan operation time clear (=)
Setting  to  resets the cumulative fan operation time to the initial value (0 [zero] time). Set this parameter
when replacing the cooling fan, and so on.
Acceleration/deceleration time setting: 0.01 to 600.0 sec. (=)
When  is set to , the acceleration/deceleration time can be set within a range of 0.01 to 600.0 sec.
Acceleration/deceleration time setting: 0.1 to 6000 sec. (=)
When  is set to , the acceleration/deceleration time can be set within a range of 0.1 to 6000 sec.
5.21

Searching for all reset parameters and changing their settings

: Automatic edit function

• Function
Automatically searches for only those parameters that are programmed with values different from the
standard default setting and displays them in the user parameter group . Parameter setting can also be
changed within this group.
Note 1: If you reset a parameter to its factory default, the parameter will no longer appear in .
Note 2: It may take several seconds to display changed parameters because all data stored in the user parameter
group  is checked against the factory default settings. To cancel the parameter group search in process,
press the
MODE
key.
E-43