Communication parameters (4-wire RS485)
These parameters allow you to change the communication speed, parity, inverter number, communication error trip
timer setting, etc. from the operation panel or an external control device.
Title
6
Function
Parity
(common to 2-wire RS485 and 4-wire RS485)
Inverter number (common)
Communications time-out time
(common to 2-wire RS485 and 4-wire RS485)
Communications time-out action *
(common to 2-wire RS485 and 4-wire RS485)
Master/slave setting for Inverter-to-inverter
communications
(common to 2-wire RS485 and 4-wire RS485)
Frequency point selection
Point 1 setting
Point 1 frequency
Point 2 setting
Point 2 frequency
Communication speed (4-wire RS485)
RS485 send waiting time
Inverter-to-inverter communication setting
(4-wire RS485)
4-wire RS485 protocol selection
(TSB/MODBUS)
Disconnection detection extended time
Inverter operation at disconnection
Adjustment range
:Non parity
:Even parity
:Odd parity
~
:OFF
~ sec.
2-wire
Setting
RS485
No action
Alarm
Trip
No action
Alarm
Trip
No action
Alarm
Trip
:Default
:Frequency command
:Output frequency
:Torque command
:Output torque command
:Disabled
:Common serial
:RS485
:Communication add option
~ %
~ (Hz)
~ %
~ (Hz)
:9600, :19200, :38400
:Default, ~ sec.
:Slave (issues a 0Hz command if
something goes wrong with the
master)
:Slave (continues operation if
something goes wrong with the
master)
:Slave (trips for emergency stop if
something goes wrong with the
master)
:Master (sends a frequency
command)
:Master (sends an output frequency)
:Master (sends a torque command)
:Master (sends an output torque
command)
:TSB
:MODBUS
~ sec.
:Inverter stop, communication
command, frequency mode open
(by CMOD, FMOD)
:None (continued operation)
:Deceleration stop
:Coast stop
:Emergency stop (E trip)
:Preset speed operation (by
setting)
F-80
E6581301
Default setting
4-wire
RS485
No action
No action
No action
Alarm
Alarm
Alarm
Trip
Trip
Trip
Inverter with a
model number
ending with
-WN:
-WP: