Setting of switching terminals
The V/f1, V/f2, V/f3 and V/f4 switching function is not yet assigned to any terminal. Therefore, it is necessary to
assign them to unused terminals.
Ex.) Assigning the V/f switching 1 function to S1 and the V/f switching 2 function to S2.
Title
S1-CC
S2-CC
V/f
6
OFF
OFF
1
ON
OFF
2
OFF
ON
3
ON
ON
4
Select V/f1 when using the vector control and the V/f-5 point setting.
Selecting V/f2,.V/f3, or V/f4 disables vector control but enables the V/f constant control. In addition, if the
torque limit switching function and the acceleration/deceleration switching function are assigned to input
terminals, the settings are valid.
Note:With the operation panel or communication, the acceleration/deceleration switching () can be set.
* This function is active only in operation panel operation mode.
Function
Input terminal function selection 5 (S1)
Input terminal function selection 6 (S2)
Base frequency 1
:
Base frequency
voltage 1
:
Manual torque boost 1 :
Thermal protection 1 :
Base frequency 2
:
Base frequency
voltage 2
:
Manual torque boost 2 :
Thermal protection 2 :
Base frequency 3
:
Base frequency
voltage 3
:
Manual torque boost 3 :
Thermal protection 3 :
Base frequency 4
:
Base frequency
voltage 4
:
Manual torque boost 4 :
Thermal protection 4 :
Adjustment range
~
~
M
S1: V/f switching 1
S2: V/f switching 2
CC
Parameters selected
Acceleration time 1
:
Deceleration time 1
:
Acceleration/
Deceleration 1 pattern :
Acceleration time 2
:
Deceleration time 2
:
Acceleration/
Deceleration 2 pattern :
Acceleration time 3
:
Deceleration time 3
:
Acceleration/
Deceleration 3 pattern :
Acceleration time 4
:
Deceleration time 4
:
Acceleration/
Deceleration 4 pattern :
F-10
E6581301
Setting value
(V/f switching 1)
(V/f switching 2)
Power running torque
limit
:
Regenerative braking
torque limit
:
Power running torque
limit
:
Regenerative braking
torque limit
:
Power running torque
limit
:
Regenerative braking
torque limit
:
Power running torque
limit
:
Regenerative braking
torque limit
: