Binary/Bcd Signal Selection (Expansion Tb Option Unit; Analog Input Signal Switching - Toshiba TOSVERT VF-AS1 Instruction Manual

The new generation high-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

Output frequency [Hz]
Set frequency
Panel key
ST-CC
S3-CC
(Jog run)

6.2.3 Binary/BCD signal selection (Expansion TB option unit)

 : 16-bit binary/BCD input selection (Expansion TB option unit)
⇒ For details, refer to Instruction Manual specified in Section 6.38.

6.2.4 Analog input signal switching

 : Analog input VI/VII voltage/current switching
 : Analog input A2 (optional circuit board) voltage/current switching
• Function
These parameters are used to switch signals to be sent to the analog input terminals VI/II and A2 (optional).
[Parameter setting]
Title

Analog VI/VII voltage/current switching
Analog input A2 (optional circuit board)

voltage/current switching
When using the analog input terminal VI/II
as a voltage input terminal (VI)
=
⇒ For an explanation of input gain and bias adjustments, refer to Section 6.28.
Forward run
RUN
STOP
Function
CCA: Analog common
CCA VI/II
0~10V input
F-5
Forward run
RUN
STOP
RUN
Adjustment range
: Voltage input
1 : Current input
: Voltage input
1 : Current input
When using the analog input terminal VI/II
as a voltage input terminal (II)
=
CCA VI/II
0~20mA(4~20mA) input
E6581301
STOP
6
Setting value