The functions assigned to the following control input terminals (contact input: ⇒ Refer to Section 7.2) are always
activated regardless of the settings of the command mode selection  and frequency setting mode selection 1
.
• Reset terminal (default setting: RES, valid only for tripping)
• Standby terminal (assigned to ST by default)
• Emergency stop terminal
To make changes in the command mode selection  and the frequency setting mode selection 1  first
stop the inverter temporarily.
No change can be made to them if the inverter is in operation.
Preset speed operation
: Set this parameter at  (terminal board).
: Any setting is valid.
1) Setting the run, stop and operation frequencies with the operation panel
Title


5
Power
supply
Function
 (Operation
Command mode selection
panel input)
Frequency setting mode
 (Operation
selection 1
panel input)
U/T1
R/L1
S/L2
V/T2
T/L3
W/T3
F
Inverter
R
ST
Shorted by a shorting bar when
shipped from the factory.
CC
CCA
RX VI/II RR/S4 PP
Default setting
Run/stop :Press the
To switch between forward run and reverse run,
use the forward/reverse run selection .
Speed command :Press the
Motor
IM
E-8
E6581301
RUN
STOP
and
on the operation panel
and
keys on the operation
panel to set the frequency.
To save the frequency,
press the ENT key. Then,
 and the set frequency
are displayed alternately for
a while.
keys