Meter adjustment 2 when the inverter is at rest (adjustment by setting  () to : Fixed output 2)
This function is useful especially in adjusting the current monitor, and the levels of items (a) to (d) in the list on the
previous page are adjusted, as described below.
(a) :The output voltage is 54% of the voltage at FM/AM when the frequency is at the maximum level ().
(b) :The output voltage at FM/AM-CC reaches 100% when the reading on the operation panel is 100%.
(c) : The output voltage at FM/AM-CC reaches 100% when the reading on the operation panel is 81%.
(d) :The output voltage at FM/AM-CC reaches 100% when the reading on the operation panel is 135%.
Meter adjustment 3 when the inverter is at rest (adjustment by setting  () to : Fixed output 3)
This function is useful especially in adjusting the torque monitor, and the levels of items (a) to (d) in the list on the
previous page are adjusted, as described below.
(a) :The output voltage is 40% of the voltage at FM/AM when the frequency is at the maximum level ().
(b) :The output voltage at FM/AM-CC reaches 100% when the reading on the operation panel is 74%.
(c) : The output voltage at FM/AM-CC reaches 100% when the reading on the operation panel is 60%.
(d) :The output voltage at FM/AM-CC reaches 100% when the reading on the operation panel is 100%.
[Example: Procedure of calibrating the meter connected to the terminal AM to which "output current" is assigned.]
Key operated
LED display
MODE


ENT
⇔
ENT
⇔
ENT


ENT
⇔

ENT
ENT
⇔
MODE
Displays the operation frequency. (Perform during operation stopped.)
(When standard monitor display selection = [Operation

frequency])
The first basic parameter "History function ()" is displayed.
Press either the
Pressing the ENTER key allows the reading of parameter setting.
Set the parameter at  (fixed output for meter calibration) by pressing

the
key.
Press the ENTER key to save the change. Then,  and the set value
are displayed alternately.
Select the AM terminal meter adjustment  by pressing the
Press the ENTER key to switch to the data display mode.
Press either the
Adjust the pointer to the graduation to which you want it to point when the
inverter passes a current 100% larger than its rated output current.
(The meter reading will change at this time but be careful because there
will be no change in the inverter's indication).
By setup, before the needle of meter beings to sway, it will take time.
Press the ENTER key to save the change. Then  and the set value are
displayed alternately.
Select the "AM terminal meter adjustment " by pressing the

Pressing the ENTER key allows the reading of parameter setting.
Return the parameter setting to  (output current display).
Press the ENTER key to save the change. Then,  and the set value
are displayed alternately.
Press the MODE key three times to return to the running frequency display
mode. (When standard monitor display selection = [Operation

frequency])
E-29
Operation
or
key to select ". "
key or the
key to adjust the meter.
[Hint]
It's easier to make the
adjustment if you push and
hold for several seconds.
E6581301
5
key.
key.