6.9
Auto-stop in case of lower-limit frequency continuous operation
: Auto-stop in case of lower-limit frequency continuous operation
• Function
If operation is carried out continuously at a frequency below the lower-limit frequency () for the period
time set , theinverter will automatically slow down the motor to a stop.
"lstp" is always displayed on the operation panel. (Blinking alternately)
This function will be canceled if a operation frequency command above the lower-limit frequency ().
[Parameter setting]
Title
Output frequency [Hz]
6
Operation signal (F-CC)
Note:This function is enabled even at the start of operation and during switching between forward and reverse run.
Function
Auto-stop in case of lower-limit frequency
continuous operation
+0.2Hz
Adjustment range
:None
~ (sec.)
F-18
E6581301
Default setting
Time [s]
ON
OFF