Periodic Maintenance Schedule; Maintenance And Repair - Vega FiberFlex LFXG-H Operating Instructions Manual

Detector with gen2000 electronics for level measurement
Table of Contents

Advertisement

Diagnostics and repair

Maintenance and repair

Periodic maintenance schedule

Since the VEGA gauge contains no moving parts, very little periodic
maintenance is required. We suggest this schedule to prevent problems
and comply with radiation regulations:

Periodic maintenance schedule

Table 5.9
Description
Standardize
Source
holder
shutter
check
Source wipe
88
Frequency
As required by process
conditions, usually at least once
a month
Every 6 months unless otherwise
required by the appropriate
nuclear regulatory body
Every 3 years unless otherwise
required by the appropriate
nuclear regulatory body
Procedure
"Calibration" chapter
Radiation safety instructions
shipped separately with
source holder and following
instructions
Radiation safety instructions
shipped separately with
source holder and following
instructions
LFXG-H Installation and Operation Guide