Advanced functions

Gauge Information

Process Variables tab

Process Variables tab — display values
Table 4.2
Value
Min PV
Max PV
Counts Low
Counts High
Sensor Temp Comp
Gain
Uniformity Gain
62
Description
The value, in process units, as entered in the setup tab.
Use this to calculate the measurement span.
The temperature and sensor uniformity gain compensated
counts from the sensor at the Cal low level. Determining
the Cal low level occurs during the calibration.
The temperature and sensor uniformity gain compensated
counts from the sensor at the Cal high level. Determining
the Cal high level occurs during the calibration.
The current value of the temperature compensation gain.
Use this to adjust for inherent sensor output change with
temperature.
The current of the uniformity gain. Use this to force all
level sensors to output the same counts at a given
radiation field. Most level applications do not use
uniformity gain and use a default of 1.0.