Conduit Torque Specifications; Gen2000 Adapter And Plugs; Wiring - Vega FiberFlex LFXG-H Operating Instructions Manual

Detector with gen2000 electronics for level measurement
Table of Contents

Advertisement

Installation

Conduit Torque Specifications

Table 2.1
Normal Size of Conduit
Inches
1/2, 3/4
1, 1-1/4 and 1-1/2
Millimeters
M16 & M20

GEN2000 Adapter and Plugs

Table 2.2
Part Number
221710
221716
2.36361
2.44134
246681
248000
247184
2.41660

Wiring

Note: If you received an interconnect drawing from VEGA or the
Use the drawing notes and the steps that follow to make the input and
output connections. Make the connections at the removable terminal strips
mounted on the power board. To access the power board, remove the
explosion-proof housing cap.
34
Plugs
"
3/4
NPT Pipe Plug
"
3/4
NPT Pipe Plug SQ HD
EEXD Approved
"
1/2
NPT Pipe Plug
"
3/4
NPT Pipe Plug
M20 x 1.5 Stop Pipe Plug
Adapters
EEXD Approved
"
3/4
NPT to 1/2
"
3/4
NPT to M20 x 1.5
"
3/4
NPT to M20 x 1.5
engineering contractor and the instructions differ from the
instructions in this manual, use the drawing. It may contain
special instructions specific to your order.
lb/ft
67
83
lb/ft
23.9
Description
"
NPT
LFXG-H Installation and Operation Guide
Torque
(N/m)
(90)
(113)
(N/m)
(32.5)
Material
Galvanized
316SS
Aluminum
316SS
Brass
Brass/unplated
Brass/unplated
316SS