Installation
L1
L2
RY NO
RY C
RY NC
Note: Not all connections are required for operation. For example,
Power
Caution: Do not apply power until thoroughly checking all wiring.
The AC power source voltage input is 100 – 230 VAC ± 10% (90 – 250
VAC) at 50/60 Hz, at 15 W (or 25 W with optional heater) maximum power
consumption.
36
Interconnecting terminals — GEN2000 with HART
Terminal 10 (-6V, Auxiliary Input Power) may not be used with
newer electronics.
The power input terminals are not polarity-sensitive.
AC or DC power input
Relay:
- normally open
- common
- normally closed
Not used in HART applications
Auxiliary input power
Common
Auxiliary input frequency signal
Current loop output