Procedure 4.9: To perform a temperature test
1. Select Diagnostics | Test | Temperature Test.
2. Click Enter.
3. Remove the gauge from control. Enter the value of the new
temperature to force.
4. Click OK.
5. The transmitter functions in this mode until it times out (1 hour), or
you click Exit and OK.

Selecting the transmitter's type and location

Gauge Setup tab

LFXG-H Installation and Operation Guide
Advanced functions
71