Advanced functions
Test
ailable:
Current Loop Test (milliamp output)
This mode manually forces the current output to a specified value. This is
useful for verifying the current loop calibration. To calibrate the current loop,
see Chapter 3: "Calibration".
Procedure 4.5: To perform a current loop test
1. Select Diagnostics | Test | Current Loop Test.
2. Click Enter.
3. Remove the gauge from control.
4. Enter the current loop test value.
5. Click OK.
The transmitter functions in this mode until it times out (1 hour), or
you click Exit and OK.
68