CLMD16 Configuration Guide___________________________________
Step 1:
Place circuit control input (Discrete I/O 1) into a "Toggle Element", then add the output of the
first "Toggle Element" into a second "Toggle Element"
Step 2:
Place the circuit control input into a "Latch Element", "Set Signal". The output of the first
"Toggle Element" goes into the "Reset Signal". Creating another "Latch Element" place the
output of the first "Toggle Element" into the "Set Signal" field. In the "Reset Signal" field place
the output of the second "Toggle Element".
Step 3:
Apply the outputs of the "Latch Elements" into the "Input Signal" field of the two load ECB
parameter dialogs. Ensure "Toggle Mode" is Off.
44
CLMD16 Configuration Guide Rev.1.1