CLMD16 Configuration Guide___________________________________
Step 1:
Populate a "Logic Element" that contains both "Binary Event High" (Connected to DC+) and
"Binary Event Low" (Connected to DC-) for the appropriate DC Input (In this example it is
"Input 4"). Where "0" is Off and "1" is On, configure the "Logic Output" in a manner to where if
any input source is On the "Logic Element's Output" becomes active.
Step 2:
Setup "Counter" where the "Increment Signal" is the "Binary Event High" signal, and the
"Decrement Signal" is "Binary Event Low". Because it is not desired to Dim down below 5% set
the "Minimum Set Point" to 5. Set the Maximum to 100. See other parameters for a generic
setting used for lighting where the "Hold Period" (Correlating to the amount of time the input
must be held before dimming) is set to 0.5s and the time in between PWM steps is 0.02s with
a PWM "Step Size" set in 1% PWM gap.
42
CLMD16 Configuration Guide Rev.1.1