6.5.3.2

Dimensioning

Recommendation
A stable power supply cannot always be assumed. Therefore, you should use
regulated power supplies to ensure the quality of the supply voltage.
The supply capacity of the fieldbus coupler/controller or the internal system
supply module can be taken from the technical data of the components.

Table 19: Alignment

Internal current consumption
Total current for I/O modules
See current catalog, manuals, Internet
*)
Example:
Calculating the current consumption on an Example Coupler:
Internal current consumption
Residual current for bus modules
Sum I
(5 V) total
The internal current consumption is indicated in the technical data for each bus
terminal. In order to determine the total requirement, add together the values of
all I/O modules in the node.
Please note the aggregate current for I/O modules. It may be necessary to
supply potential!
When the sum of the internal current consumption for the I/O modules exceeds
their aggregate current, you must use a supply module with bus power supply.
Install it before the position where the permissible aggregate current would be
exceeded.
Manual
Version 1.3.0
750-xxxx/040-xxx System Manual XTR
*)
Current consumption via system voltage
(5 V for electronics of I/O modules and
fieldbus coupler/controller).
*)
Available current for the I/O modules.
Provided by the bus power supply unit.
See fieldbus coupler/controller and internal
system supply module
380 mA at 5 V
1620 mA at 5 V
2000 mA at 5V
WAGO I/O System 750 XTR