System Supply; Connection; Figure 18: System Voltage For Fieldbus Couplers/Controllers (Example); Table 18: Legend For Figure "System Voltage For Fieldbus Couplers - WAGO 750 XTR Manual

Hide thumbs Also See for 750 XTR:
Table of Contents

Advertisement

50
Connect Devices
6.5.3

System Supply

6.5.3.1

Connection

The WAGO I/O System 750 requires a 24 V direct current system supply.
The power supply is provided via the fieldbus coupler/controller and, if necessary,
in addition via internal system supply modules "System Power Supply 24 VDC
XTR
(750-613/040-000)". The power supply is reverse voltage protected.
Do not use an incorrect voltage/frequency!
The use of an incorrect supply voltage or frequency can cause severe damage to
the components.

Figure 18: System Voltage for Fieldbus Couplers/Controllers (Example)

Table 18: Legend for Figure "System Voltage for Fieldbus Couplers/Controllers"
Position
1
2
The fed-in 24 VDC supplies all internal system components, e.g. fieldbus
coupler/controller electronics, fieldbus interface and I/O modules via the local bus
(5 VDC system voltage). The 5 VDC system voltage is galvanically connected to
the 24 VDC supply voltage.
Manual
Version 1.3.0
Description
System supply 24 VDC
System supply 0 V
WAGO I/O System 750 XTR
750-xxxx/040-xxx System Manual XTR