Functionality Tests - Cls300 - Siemens Pointek CLS200 Operating Instructions Manual

Capacitance switches
Hide thumbs Also See for Pointek CLS200:
Table of Contents

Advertisement

Wiring

6.5 Functionality tests - CLS300

6.5
Functionality tests - CLS300
To test the basic functionality of the probe and potentiometers:
Switches shown in OFF
position
Preparation
1. Ensure green power light L3 is on.
2. Turn the delay potentiometer P1 fully clockwise (minimum delay).
3. Set dip switches S1 to S4 OFF (full potentiometer control activated).
4. Set switch S5 ON (high sensitivity).
Test Procedures
Test the sensitivity of the sensor:
• If the yellow sensor status LED (L1) is on, turn potentiometer P2 clockwise until it turns
off.
• Slowly turn the trip point potentiometer P2 counter-clockwise until the yellow sensor
status light L1 glows. Shortly afterwards, the red output status light L2 will glow. This
concludes the sensitivity test.
Test the delay:
1. Turn the trip point potentiometer P2 clockwise, until the yellow sensor status LED L1 turns
off.
2. Turn the delay potentiometer P1 about 1/8 turn clockwise (delay set point).
3. Slowly turn the trip point potentiometer P2 counter-clockwise until the yellow sensor status
light L1 glows. After an appropriate delay the red output status light L2 will glow. This
concludes the delay test.
Test the switch function:
1. Turn the delay potentiometer P1 fully counter-clockwise.
2. Turn the trip point potentiometer P2 clockwise until the yellow sensor status LED L1 is off.
34
Pointek CLS200/CLS300 standard
Operating Instructions, 05/2021, A5E47827796-AA