The power supply is galvanically isolated and can accept voltages in the range 12 to 250 V
AC/DC, depending on the application. The materials used in the probe construction provide a
high level of chemical resistance, and an excellent temperature rating on the process wetted
portion of the probe: up to 125 °C (257 °F) for the CLS200 and 400 °C (752 °F) for the
CLS300.
Modular design and construction provide a wide choice of configurations, including rod,
cable, and sanitary versions. When used with a SensGuard protection cover, the CLS200
sensor is protected from shearing, impact, and abrasion, in tough primary processes.
Refer to Technical data (Page 50) for CE applications.
1)
4.1

Pointek CLS200/300 applications

Pointek CLS200/300 is designed for level detection and simple pump control in a variety of
applications:
• Liquids, solids (powder and granules), slurries, interface detection (for example, oil/
water), and foam detection
• Foods and pharmaceuticals
• Chemical and petrochemical
• High pressure and temperature