6.4
Functionality tests - CLS200
To test the basic functionality of the probe and potentiometers:
Switches shown in OFF
position
Preparation
1. Ensure the green power LED L3 is on.
2. Set DIP switches S1 to S4 OFF (rocker down as shown in diagram above).
3. Set DIP switch S5 ON (rocker up, opposite to diagram above).
4. Turn the delay potentiometer P1 fully counter-clockwise.
5. If the yellow sensor status LED L1 is not on, turn the trip-point potentiometer P2 counter-
clockwise until it just turns on.
6. Turn the trip-point potentiometer P2 clockwise until LED L1 just turns off.
7. Set DIP switch S5 OFF (rocker down as shown in diagram above).
Test Procedures
Test the switch function:
• Grasp the probe with your hand. LED L1 should turn on. LED L2 should turn on after a
slight delay, and the output relay may provide an audible click.
Test the delay:
1. Grasp the probe with your hand. L1 should turn on (glow) immediately. The red output
status LED L2 should turn on after a delay.
2. Turn the delay potentiometer P1 clockwise about 1/8 of a turn.
3. Grasp the probe with your hand. L1 should turn on immediately, but L2 should turn on after
a longer delay than in Step 1.
Pointek CLS200/CLS300 standard
Operating Instructions, 05/2021, A5E47827796-AA
6.4 Functionality tests - CLS200
Wiring
33