Other Approvals; Emc And Environmental Type Tests - Siemens SIMATIC NET RUGGEDCOM RS950G Equipment Manual

Rugged ethernet switches
Hide thumbs Also See for SIMATIC NET RUGGEDCOM RS950G:
Table of Contents

Advertisement

Certification
6.1.10 Other Approvals
Declarations of conformity for each directive are available online via
Industry Online Support
6.1.10

Other Approvals

This device meets the requirements of the following additional standards:
6.2

EMC and Environmental Type Tests

The RUGGEDCOM RS950G has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
30
EU RoHS Directives (EU) 2011/65 and (EU) 2015/863
European Directive for Restriction of Hazardous Substances
China RoHS (relating to SJ/T 11364)
Management Methods for the Restriction of the Use of Hazardous Substances in
Electrical and Electronic Products
[https://support.industry.siemens.com/]>.
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications
Networking Devices in Electric Power Substations
IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General
Requirements
Test
Description
ESD
Radiated RFI
Burst (Fast
Transient)
Surge
Enclosure
Contact
Enclosure Air
Enclosure Ports
Signal Ports
± 4 kV @ 2.5 kHz
DC Line-to-Line
AC Line-to-Line
Earth
Ground Ports
Signal Ports
± 4 kV Line-to-Ground,
± 2 kV Line-to-Line
DC Line-to-Line
± 2 kV Line-to-Ground,
± 1 kV Line-to-Line
AC Line-to-Line
± 4 kV Line-to-Ground,
± 2 kV Line-to-Line
Siemens
Test Levels
± 8 kV
± 15 kV
20 V/m
RUGGEDCOM-
severity levels.
± 4 kV
± 4 kV
± 4 kV
Equipment Manual, 10/2023, C79000-G8976-1037-08
Severity
Levels
4
4
specified
a
Note
4
4
4
4
3
4
RUGGEDCOM RS950G

Advertisement