Certification
6.1.8 RoHS
A copy of the Declaration of Conformity is available via Siemens Industry Online
Support at https://support.industry.siemens.com/cs/ww/en/view/89855782.
6.1.8
RoHS
This device is declared by Siemens Canada Ltd. to meet the requirements of the
following RoHS (Restriction of Hazardous Substances) directives for the restricted use
of certain hazardous substances in electrical and electronic equipment:
•
•
Declarations of conformity for each directive are available online via
Industry Online Support
6.1.9
Other Approvals
This device meets the requirements of the following additional standards:
•
6.2
EMC and Environmental Type Tests
The RUGGEDCOM i803 has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
30
EU RoHS Directives (EU) 2011/65 and (EU) 2015/863
European Directive for Restriction of Hazardous Substances
China RoHS (relating to SJ/T 11364)
Management Methods for the Restriction of the Use of Hazardous Substances in
Electrical and Electronic Products
[https://support.industry.siemens.com/]>.
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity
for Industrial Environments
Test
Radiated RFI
Burst (Fast Transient)
Induced (Conducted) RFI
Description
ESD
Enclosure
Contact
Enclosure Air
Enclosure ports
Signal ports
DC Power ports
Surge
Signal ports
DC Power ports
Signal ports
DC Power ports
Siemens
Test Levels
± 4 kV
± 8 kV
± 8 kV
20 V/m
± 4 kV @ 5 kHz
± 4 kV @ 5 kHz
± 1 kV line-to-earth
± 0.5 kV line-to-earth/line
10 V
RUGGEDCOM i803
Equipment Manual, 10/2023, C79000-G8976-1005-09
Need help?
Do you have a question about the SIMATIC NET RUGGEDCOM i803 and is the answer not in the manual?