Siemens Pointek CLS200 Operating Instructions Manual page 104

Capacitance switches
Hide thumbs Also See for Pointek CLS200:
Table of Contents

Advertisement

Shortening the cable
E.1 Pointek CLS200 Standard, cable version
11.Prepare the leads for soldering, and if heat shrink is used to insulate splices, remember to
slip on the heat shrink before soldering the leads.
12.Make the solder connections and position the heat shrink to completely insulate each solder
connection before shrinking it.
13.Remove any excess cable core, if necessary.
14.Apply PTFE type tape/sealant to all threads.
15.Add a pre-twist to the wires before screwing the probe sleeve and lower probe assembly
together: hold the probe sleeve still, and gently turn the lower probe assembly counter-
clockwise about 5 full turns. This avoids the wires being broken when the probe and probe
sleeve are assembled.
16.Screw the lower probe assembly clockwise into the probe sleeve, and tighten it with a 17
mm (0.67") wrench.
See also
Functionality tests - CLS200 (Page 33)
104
Steel spacer
Tension block
Core
Pointek CLS200/CLS300 standard
Operating Instructions, 05/2021, A5E47827796-AA

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pointek cls300

Table of Contents