Sensitivity setting (high or low): S5
S5-ON
S5-OFF
Test settings: S4
When S4 is set to ON, it inverts the signal, allowing you to test the delay settings from P1, or
to verify that S1 and S2 are in the correct position.
S4-ON
S4-OFF
7.2.1.4
Setup
It is essential to check settings during the process itself, and confirm that they are correct,
before regular operation commences.
Initial setup can be carried out prior to mounting into the process, but it is extremely
important to calibrate the unit and adjust the sensitivity on the product itself.
For a simple application, set Pointek CLS300 to Low alarm/no delays:
• turn P1 fully counter-clockwise (no delay interval)
• set dip switches S1, S2 and S5 to ON, S3 and S4 to OFF
S1-ON
S2-ON
S3-OFF
S4-OFF
S5-ON
7.2.1.5
Start up
After Pointek CLS300 is properly mounted and the switch bank is set up, apply power to the
unit. The green LED (L3) glows, indicating the unit is powered and operational.
Pointek CLS200/CLS300 standard
Operating Instructions, 05/2021, A5E47827796-AA
High sensitivity
Low sensitivity
Enable test
Normal operation
WARNING
Delay disabled
Delay disabled
Low alarm
Test function disabled
High sensitivity
Use this setting for measuring dry solids or nonconductive
liquids.
Use this setting for measuring conductive liquids, or viscous
conductive solids that can build up on the sensor
Observe the response of the output status and sensor status LEDs
to verify the delay interval set by potentiometer P1.
•
probe uncovered = alarm ON/relay deenergized
•
normal operation
•
default setting
•
for dry solids or non-conductive liquids
Operation
7.2 Pointek CLS300
45