Features of UMG511
• Front panel installation, 144x144mm
• Working temperature range - 10°C - +55°C
• Colour graphics display 320x420, 256 colours, 6 push buttons
• 8 digital inputs, 5 digital outputs
• 16Bit A/converter, data memory 256MByte flash, SDRAM 32Mbyte,
• Continual scanning of voltage and current measurement inputs with 20kHz,
• frequency of fundamental oscillation 15Hz..440Hz
• 4 voltage measurement inputs, 4 current measurement inputs,
• measurement in TN and TT networks,
• RS485
-
Profibus DP/V0 (Option)
- Modbus RTU, Modbus-Master, BACnet (Option)
• Ethernet Web-Server, EMAIL, BACnet (Option),
• collection of transients >50µs and storage with up to 16000 scanning points,
• collection of more than 2000 measurement values,
• measurement of the network quality according to DIN EN61000-4-30, class A,
• Flicker measurement according to DIN EN61000-4-15,
• analysis and assessment according to DIN EN50160 with the GridVis programming software
included in the delivery.
• Working measurement, measurement uncertainty according to DIN EN50470-3
- Class C for ../5A converter
- Class B for ../1A converter
• Measurement of harmonics 1 to 63 according to DIN EN 61000-4-7 class 1 for
- Ull, Uln, I, P (receipt/supply) and
- Q (ind/cap).
• Measur. of intermediate harmonics 1 to 63 for (Uln, Ull, I) according to DIN EN61000-4-7 cl. 1,
• programming of own applications in Jasic