Technical data
Measurement uncertainty
Measurement uncertainty of the UMG511 applies to application within the measurement ranges.
The measurement value must be within the stated limits. Measurement uncertainity is not speci-
fied outside of these limits.
The specification applies under the following conditions:
• Annual recalibration,
• a pre-heating time of 10 minutes,
• an environmental temperature of 18..28°C.
If the device is operated outside a range of 18..28°C, an additional measurement error of ±0.01%
deviation from the measurement value per °C must be considered.
70