2gig Technologies EDGE Installation Manual

2gig Technologies EDGE Installation Manual

Security & smart home system
Hide thumbs Also See for EDGE:
Table of Contents

Advertisement

PRINTER'S INSTRUCTIONS:
INSTR, INSTL, 2GIG-EDG-NA, PN:10025596 Rev-A
BLACK, 20LB MEAD BOND, 8.5"A", TOL. +/- 0.125",SCALE: 1:1, FRONT & BACK, FOLDING: ALBUM FOLD - BINDING: SADDLE-STITCH
TM
2GIG EDGE
TM
Security & Smart
Home System
INSTALLATION
GUIDE

Advertisement

Table of Contents
loading

Summary of Contents for 2gig Technologies EDGE

  • Page 1 PRINTER'S INSTRUCTIONS: INSTR, INSTL, 2GIG-EDG-NA, PN:10025596 Rev-A BLACK, 20LB MEAD BOND, 8.5”A”, TOL. +/- 0.125",SCALE: 1:1, FRONT & BACK, FOLDING: ALBUM FOLD - BINDING: SADDLE-STITCH 2GIG EDGE Security & Smart Home System INSTALLATION GUIDE...
  • Page 2: Table Of Contents

    To connect an external alarm sounder to the 2GIG EDGE Panel:.......
  • Page 3: Introduction

    Q505: Trouble restore reports to CS ..............53 This guide is designed for distributors, alarm dealers, and professional installers of the 2GIG EDGE Security & Smart Home System. It provides Q506: Manual bypass reports to CS .
  • Page 4: Taking Security Innovation To The Edge

    24-Hour Backup Battery: A 24-hour backup battery to support the 2GIG EDGE Panel during temporary AC power failures and outages. » USB Port: A convenient USB port at the top of the 2GIG EDGE Panel that can be used with a USB thumb drive (not supplied) to update the system’s firmware. »...
  • Page 5: Internal Components

    Recessed Door/Window Contacts. Sensors might also be installed in additional locations, such as a Glass Break Detector and a Passive Infrared Motion Detector. NOTE: A variety of 2GIG and GoControl branded devices are compatible with the 2GIG EDGE Security & Smart Home System. Sensors manufactured by other companies may also be compatible with the system. For information, visit dealer.2gig.com...
  • Page 6: For Residential Settings

    Avoid choosing a location in direct sunlight. Less DOOR DOOR than NOTE: If mounting the 2GIG EDGE Panel on a wall is not an option, the 2GIG Desktop Kit can be purchased for use with the 2GIG EDGE 3 ft Large Wall above Security &...
  • Page 7: Where To Place Burglary Protection Sensors

    FRONT AND SIDE DOOR SENSORS 1 . Mount the antenna plate as high as possible on a wall or in the attic (A). (WITH ENTRY/EXIT DELAY) 2 . Drop the antenna’s 10-foot cable down to the 2GIG EDGE Panel (B). ENTRY LIVING...
  • Page 8: Connect The Antenna

    Jumper Wire Jumper Terminal 3 . Insert the exposed wire from Step 1 into the available foam holder to isolate it from exposure to other board components. Insert Wire 2GIG EDGE Installation Guide Copyright © 2021 Nortek Security & Control LLC...
  • Page 9: Mount The Panel

    Mount the Backplate to a Wall The terminal block inside the 2GIG EDGE Panel includes two (2) solid-state bell terminals (BELL+/BELL-) for an external alarm sounder. An external alarm sounder is typically housed outside of a property, in a location that will attract the most attention, in order to scare unwanted intruders...
  • Page 10: Connect The Hardwire Loops

    TAKE-KIT1) . The most common way to connect the AC power supply for the 2GIG EDGE Panel is to use the system’s terminal block. This requires you securely fasten 2- conductor power wire (not supplied) to the appropriate DC IN+/DC IN– screw terminals.
  • Page 11: Connect Power (Barrel Connector)

    Connect the Backup Battery 5 . Ensure the backup battery is properly seated in the 2GIG EDGE chassis. The battery’s label should be facing up and the battery’s connector wire should be on the left with the wire running in the empty space between the battery compartment.
  • Page 12: Terminal Blocks Wiring Diagram

    Replacing the Battery (continued) Terminal Blocks Wiring Diagram The 2GIG EDGE Panel includes an 8-position terminal block and a 6-position terminal block. The table below describes each position on the terminal blocks. NOTE: Terminal block accommodates up to 18 gauge wire.
  • Page 13: Control Panel Wiring Diagram

    Control Panel Wiring Diagram 1 . Ensure all installed wiring is securely fastened. 2 . Place the upper lip of the back of the panel chassis over the back top of the backplate, then flip the Edge Panel downward. Hardware loops can be programmed as normally 3 .
  • Page 14 The Installer Toolbox is password-protected. To use this feature, you must enter an Installer Code. The factory default code is 1561. As 2GIG releases firmware updates for the 2GIG EDGE Panel, download the update to a USB thumb drive and then connect it to the USB port on the 2GIG EDGE Panel.
  • Page 15 06-24-Hour Silent Alarm 07- 24-Hour Audible Alarm 24-Hour Auxiliary Alarm 10-Interior with Delay 23-No Response Type in “Sensor Type" above, you must also select this option ( continued next page 2GIG EDGE Installation Guide Copyright © 2021 Nortek Security & Control LLC...
  • Page 16 ➣ Normally Closed (NC): Sends alert signal to the security system when the sensor’s circuit is no longer in the NC state. End-of-Line Resistor (EOL): Choose when an end- of-line (EOL) resistor is present. 2GIG EDGE Installation Guide Copyright © 2021 Nortek Security & Control LLC...
  • Page 17 1 . Highlight Smart Areas Assignment. 2 . Under Smart Areas Assignment, choose a Smart Area (Partition) for the keyfob. 3 . Tap t to move to the next option. 2GIG EDGE Installation Guide Copyright © 2021 Nortek Security & Control LLC...
  • Page 18 4 . Tap the matching vocabulary word above the touchscreen keypad to select it. 5 . Repeat the steps above to enter the desired phrase for the keypad. NOTE: 2GIG Edge panel and Remote Keypads must be connected 6 . Tap Done.
  • Page 19 7 . Tap t to move to the next option. 2 . Tap t to move to the next option. After Image Sensors have been added to the 2GIG EDGE Panel in Wireless Zones programming, the Image Sensor details will be displayed in Image Sensor settings.
  • Page 20 2 . Tap Connect. 3 . Tap  to go back to the Network Settings menu. 3 . Locate and press the WPS on your router. 2GIG EDGE Panel will securely connect with the router. 4 . Once Authorization is successful, tap ACCEPT.
  • Page 21 ➣ Tap Sensors Tests, then walk to and trigger each sensor. 4 . If edits have been made, tap SAVE SETTINGS to save. NOTE: Make a note of SSID and Password for use in WiFi setup of 2GIG EDGE Remote Keypads, approved video doorbells and cameras.
  • Page 22 Q105: 2-way voice Configures the system to automatically turn the 2GIG EDGE Panel’s 2-Way Voice feature ON or OFF after the type of alarm you specify. This gives the 2GIG EDGE Panel’s Cellular Radio Module the ability to automatically dial the Central Station and connect with an operator after an alarm sounds.
  • Page 23 Smart Area. Users can be assigned and control assigned Smart Areas. Smart Areas Settings will allow naming of Away Mode at the 2GIG EDGE Panel. If no one exits that door before the Exit Delay countdown expires, the system automatically arms itself in Stay all four areas.
  • Page 24 Typically, secondary entrances that require a slightly longer entry time are programmed as an Exit/Entry 2 door. For example, a back, side, or garage entry door. When a user enters the premises while the system is armed, the Entry Delay 2 countdown starts. The 2GIG EDGE Q123: Cross sensor zones 99-100 Panel beeps once every two (2) seconds during the countdown.
  • Page 25 2GIG EDGE Panel is without AC power for 10 minutes. When AC power is restored to the 2GIG EDGE Panel, the trouble alert condition clears automatically after one (1) minute.
  • Page 26: Q307: Open Collector #1 Output

    Q303: Emergency key page Configures the system to show or hide the Emergency button on the Alarm screen of the 2GIG EDGE Panel’s touchscreen. When set to Audible, the NOTE: The factory default setting for Open Collector Output #2 is 00-Disabled button is visible and the system emits a loud, patterned warning siren when a user sets off an emergency alarm on the 2GIG EDGE Panel.
  • Page 27: Q405: Broadband Network Failure Causes Trouble

    NOTE: Bypass setting on Alarm.com monitoring settings supersedes Q506: Manual bypass reports to CS. Configures the system to activate a trouble condition if one of the 2GIG EDGE Panel’s tamper switches (wall tamper switch or cell radio tamper switch) is triggered while the system is disarmed. The system will also activate an alarm condition if a tamper switch is triggered while the Q507: Bypass restore reports to CS system is armed.
  • Page 28: Q509: Ac Loss Reports To Cs

    Reports are not sent if a sensor is in swinger shutdown until the time of disarm and the sensor is closed. Configures the system to transmit a report to the Central Station when AC power is restored to the 2GIG EDGE Panel. When enabled, AC power »...
  • Page 29: Panel Programming

    Stay or Away mode. (32) Remote Special Zone with Wireless Repeater Device † Indicates sensor types that are not allowed for hardwired loops. 2GIG EDGE Installation Guide Copyright © 2021 Nortek Security & Control LLC...
  • Page 30: Transmission Id (Txid)

    Turns the Transmission Delay feature OFF Lock (135), Loft (136), Low (137) 1070-2GIG Fall Detector Pendant (2GIG -F1-345) *NOTE: eSeries sensors are only compatible with the 2GIG EDGE panel. Main (138), Maintenance (139), Man (281), Master (140), Medical Voice Descriptor...
  • Page 31: Sensor Supervised

    Allow quick exit Enabled System Configuration Chime #2 with Voice Disabled Enabled Q117 Quick bypass Disabled System Configuration Disabled Enabled Q118 Auto unbypass for manual bypass Enabled System Configuration Disabled 2GIG EDGE Installation Guide Copyright © 2021 Nortek Security & Control LLC...
  • Page 32 Troubles Disabled Disabled Disabled Enabled Q409 System tamper causes trouble Enabled Troubles 15 Seconds Disabled Q212 Siren supervision time Disabled Timers, Delays & Counts 30 Seconds 45 Seconds 2GIG EDGE Installation Guide Copyright © 2021 Nortek Security & Control LLC...
  • Page 33: Ansi/Sia Cp-01-2010 Features To Limit False Alarms

    “Q115: Exit delay restart” Enabled Q504 Trouble reports to CS Enabled Reporting Disabled 4.2.2.4 Exit Error Exit Error See the 2GIG EDGE User Guide Enabled Q505 Trouble restore reports to CS Enabled Reporting 4.2.2.5 Unvacated Premises Auto Stay “Q114: Auto stay”...
  • Page 34: Limited Warranty

    The Alarm is equipped with a warning siren. Exposure to high sound levels or prolonged exposure to the warning siren can result in Noise Induced Hearing Loss (NIHL) 10025596 Rev-A 2GIG EDGE Installation Guide Copyright © 2021 Nortek Security & Control LLC...