Download Print this page

HTC 2500 iX Manual page 264

Advertisement

MANUTENZIONE
Generatore tipo 28-31-32.
Procedura di verifica per diodi rotore
eccitatrice.
Strumentazione necessaria :
batteria 12V
lampada 12V-21W (o in alternativa
resistenza 6.8Ω-30W)
voltmetro (Ex. Multimetro su scala
VOLT d.c.)
Importante: Prima di eseguire le
operazioni seguenti sconnettere i due
cavi
di
collegamento
principale al ponte diodi (+ e -).
TEST DEI DIODI SUL "NEGATIVO"
Connettere gli strumenti come
indicato in figura A (tabella 26 pag.
74)
Fissare il cavo connesso alla
lampada al morsetto negativo del
ponte come indicato in figura A
(tabella 26 pag. 74)
Connettere il terminale "Probe" ai
punti A1, A2 ed A3 in sequenza per
verificare rispettivamente i diodi 1, 2
e 3. Verificare la lettura sul voltmetro
in relazione a quanto indicato in
tabella (tabella 26 pag. 74).
TEST DEI DIODI SUL "POSITIVO"
Connettere gli strumenti come
indicato in figura B (tabella 26 pag.
74)
Fissare il cavo connesso al negativo
della batteria al morsetto positivo del
ponte come indicato in figura B
(tabella 26 pag. 74)
Connettere il terminale "Probe" ai
punti A4, A5 e A6 in sequenza per
verificare rispettivamente i diodi 4, 5
e 6; verificare la lettura sul voltmetro
in relazione a quanto indicato in
tabella (tabella 26 pag. 74).
ISTRUZIONI PER LA SOSTITUZIONE
DEL DIODO.
Qualora i valori riscontrati indichino un
d i o d o
d a n n e g g i a t o ,
procedere
alla
sostituzione
componente.
A tale scopo si raccomanda di non
estrarre i reofori dalle rispettive sedi ma
di tagliarli in prossimità del corpo del
c o m p o n e n t e ;
i n s e r i r e
componente rispettando le polarità e
saldare a stagno accuratamente i reofori
con gli spezzoni rimasti nelle sedi.
del
rotore
-
+
o c c o r r e r a '
del
i l
n u o v o
IMPORTANTE
IMPORTANT
WICHTIG
46
MAINTENANCE
Generator versions: 28-31-32.
Procedure to check the diodes of the
exciter rotor.
Necessary equipment :
12V battery
12V-21W lamp (or alternatively 6.8Ω-
30W Resistance)
Voltmeter (for instance, multimeter
on scale VOLT d.c.)
Warning:
before
performing
following actions, it is necessaty to
disconnect the 2 cables connecting
the main rotor to the diode bridge
(+and-)
TEST OF THE DIODES ON THE
"NEGATIVE"
Connect the equipment, as it is
pointed out in the picture A (table 26
page 74)
Fix the cable connected to the lamp
to the negative terminal of the bridge,
as it is pointed out in the picture A
(table 26 page 74)
Connect the terminal "Probe" to the
point A1 (it is checked the diode 1),
then to the point A2 (it is checked the
diode 2) and finally to the point A3 (it
is checked the diode 3); check the
readings on the voltmeter in relation
with what is reported on the table
(table 26 page 74).
TEST OF THE DIODES ON THE
"POSITIVE"
Connect the equipment, as it is
pointed out in the picture B (table 26
page 74)
Fix the cable connected to the
negative terminal of the battery to the
positive terminal of the bridge, as it is
pointed out in the picture B (table 26
page 74)
Connect the terminal "Probe" to the
point A4 (it is checked the diode 4),
then to the point A5 (it is checked the
diode 5) and finally to the point A6 (it
is checked the diode 6); check the
readings on the voltmeter in relation
with what is reported on the table
(table 26 page 74).
INSTRUCTIONS TO REPLACE
THE DIODE
When the values measured point out a
diode damaged, it is necessary to
replace the component.
For this purpose it is recommended to
not pull the rheophores out from their
locations, but to cut them near to the
body of the component; then fit in the
new component respecting the polarity
and soft-solder
accurately the
rheophores with the pieces remained in
their locations.
ECO-ECP MANUAL January 2012 revision 30
the

Advertisement

Chapters

loading