Unpacking And Checking - Huawei UPS5000-S Series User Manual

50 kva-300 kva
Hide thumbs Also See for UPS5000-S Series:
Table of Contents

Advertisement

UPS5000-S-(50 kVA-300 kVA)
User Manual
Model
a: recommended when the short-circuit current where the switch is located is less than 36 kA

3.1.4 Unpacking and Checking

Context
● To prevent the UPS from falling over, secure it to a pallet truck using ropes
● To prevent shocks or falls, move the UPS gently. After placing the UPS in the
● To prevent dust from settling on the UPS, leave the original plastic coat on until
Procedure
Step 1 Use a pallet truck to transport the UPS to the installation position.
Step 2 Check the UPS packing.
Step 3 Hold the sliding plate steady. Cut and remove the binding tapes. Put down the
sliding plate gently.
Issue 11 (2020-12-07)
UPS Capacity
300 kVA
NO TE
● The input upstream circuit breakers recommended in
● If multiple loads are connected, specifications for branch circuit breakers must not
exceed the recommended specifications.
● The circuit breaker selection principle is to protect loads and cables, and the cascading
principle is to realize specific protection.
NO TICE
before moving it.
installation position, unpack it and take care to prevent scratches. Keep the UPS
steady during unpacking.
installation is required.
Copyright © Huawei Technologies Co., Ltd.
Component
Downstream output circuit
breaker
Mains input circuit breaker
Bypass input circuit breaker
Downstream output circuit
breaker
3 Installation
Specifications
400 A/3P
630 A/3P
630 A/3P
630 A/3P
Table 3-6
are for reference only.
a
60