Huawei UPS5000-S Series User Manual page 155

50 kva-300 kva
Hide thumbs Also See for UPS5000-S Series:
Table of Contents

Advertisement

UPS5000-S-(50 kVA-300 kVA)
User Manual
Figure 4-12 Comm settings (lithium battery)
Figure 4-13 IP settings
IP address allocation
Issue 11 (2020-12-07)
If the MDU is directly connected to a computer, the IP address can only be
allocated manually. The IP addresses of the MDU and computer must be in
the same network segment, and must be different.
If the MDU is connected to a computer through a LAN switch or router with
the DHCP function, the IP address can be allocated manually or automatically.
Manual allocation is used by default.
Manual: Check that their IP addresses are two different values on the
same network segment. Set the UPS IP address to be in the same subnet
as the PC IP address. Perform the bitwise AND operation for the UPS IP
address and the PC IP address with the subnet mask respectively. If the
operation results are the same, the two IP addresses are in the same
subnet.
AND operation rule: 1 AND 1 = 1, 1 AND 0 = 0, 0 AND 1 = 0, 0 AND 0 =
0. That is when the corresponding bits are both 1, the result is 1. In other
cases, the result is 0.
Table 4-10 Bitwise AND operation example
N/A
PC IP address/UPS IP
address
Subnet mask
(255.255.255.192)
Copyright © Huawei Technologies Co., Ltd.
PC IP address
(182.98.225.125)
10110110.01100010.1
1100001.01111101
11111111.11111111.1
1111111.11000000
4 User Interface
UPS IP address
(182.98.225.112)
10110110.01100010.1
1100001.01110000
11111111.11111111.1
1111111.11000000
145