Huawei UPS5000-S Series User Manual page 187

50 kva-300 kva
Hide thumbs Also See for UPS5000-S Series:
Table of Contents

Advertisement

UPS5000-S-(50 kVA-300 kVA)
User Manual
Item
RAM verification
Record time after
fault
Collect real-time
site waveform
Fan life
BCB trips in case
of EOD
Table 4-13 Input settings
Item
Input
adaptability
Issue 11 (2020-12-07)
Description
Enable or disable the memory check
function. If this parameter is set to
Enable, the control chip RAM working
status is checked regularly. If this
parameter is set to Disable, regular
check is disabled.
Indicates the time for storing fault data
after the UPS experiences a fault. The
default value is 0 ms, which means that
the data during 20 ms before the fault
occurs is recorded. If the value is set to
40 ms, it means that the data during 20
ms before the fault occurs and the data
during 40 ms after the fault occurs are
recorded, and the like.
If this parameter is set to Enable, one
waveform can be stored manually.
Indicates the life detection for fans in the
power modules and bypass module.
If this parameter is set to Enable, the
BCB will trip in case of EOD.
Description
Input adaptability mode 1: It is
applicable to the normal power
grid and DGs, and DGs that are
sensitive to the output reactive
component. Input adaptability
mode 2: It is applicable to the
normal power grid and DGs, and
input power sources with high
internal resistance.
Copyright © Huawei Technologies Co., Ltd.
Default Value
Value Range
Disable
Disable, Enable
0 ms
0 ms, 20 ms, 40
ms, 60 ms, 80
ms
Disable
Disable, Enable
Enable
Disable, Enable
Enable
Disable, Enable
Default
Value
Mode 2
4 User Interface
Value
Range
Mode 1,
Mode 2
177