Figure 3-73 Connecting signal cables
----End

3.2.9 Routing Cables (UPS5000-S-300K-SMT)

Context
● Route cables for the UPS from inside out.
● When connecting battery cables, you do not need to connect neutral wires.
Procedure
Step 1 Ensure the maintenance bypass switch is OFF. Open the front door and remove
the cover from the power distribution subrack.
Issue 11 (2020-12-07)
NO TE
The number and colors of signal cables in
NO TICE
Copyright © Huawei Technologies Co., Ltd.
Figure 3-73
are for reference only.
3 Installation
111