UPS5000-S-(50 kVA-300 kVA)
User Manual
Figure 5-15 Starting a capacity test
----End

5.6.3 Test Data Download

Issue 11 (2020-12-07)
NO TE
The capacity test automatically stops in any of the following cases:
● The minimum cell voltage reaches 2.6 V.
● The load fluctuation exceeds 10%.
● An alarm is generated.
The test is complete when the minimum cell voltage reaches 2.6 V. Data about the most
amount of energy discharged is stored once a month for 36 months.
Web
a.
On the WebUI, choose Query > Operation Log, choose logs that need to
be queried from the Log drop-down list box, and click Query.
Figure 5-16 Operation Log
b.
Choose logs that have been queried from the Log drop-down list box,
and click Export.
Old Web
a.
On the WebUI, choose Query > Logs, choose logs that need to be
exported from the Log drop-down list box, and click Query.
Figure 5-17 Logs