Procedure
Step 1 On the LCD, set System Info > Settings > System Settings > Working mode to
ECO. The information indicating that the UPS works in ECO mode is displayed on
the LCD.
Step 2 Set the ECO voltage range.
Figure 5-9 ECO parameters
Step 3 (Optional) If you set ECO mode in bypass mode, manually start the UPS inverter.
After the inverter starts, the UPS still works in bypass mode and the inverter is on
standby. If the bypass is not normal, the inverter supplies power immediately. If
the inverter is not started, the UPS may be disconnected.
Figure 5-10 System status in ECO mode
----End

5.6 Testing Batteries

Issue 11 (2020-12-07)
NO TICE
Copyright © Huawei Technologies Co., Ltd.
5 Operations
229